Collector Tube Efficiency Thermomax collectors are tested by European and North American authorities. The test results of Institute SPF at the Hochschul Rapperswil of Switzerland leads to following thermal performance equations (Test Report No. 264, August 1997): Efficiency of Collector = 0.84 - 2.02 (Tm-Ta)/G - 0.0046G[(Tm-Ta)/G]**2
Tests conducted by Florida Solar Energy Center of USA (FSEC Solar Collector Test Report No. 97005, May 1998) is in very good agreement with the performance test reported by SPF Institute: Efficiency
of Collector = 0.82 - 2.19 (Tm-Ta)/G where: These test results are shown
in the following graph: Thermomax
offers following measured
efficiency curve of the
Thermomax and Mazdon collector system: Thermomax evacuated solar collectors are specifically designed for all-year-round operation in regions with cold winters and also locations with high humidity such as the tropics. The following chart shows a practical approach to find collector tube efficiency for various insolation levels.
Collector Temperature of 60 degrees C (140 F) with an ambient temperature of 20 degrees C (68 F) and insolation of 800 W/m gives a collector efficiency of 69%. |
|